Yelantra_logo


Single Phase Online UPS Products  
Quanta_Batteries

ML 31T

The ML31T series is a three phase to single phase online UPS with transformer. It is suitable for inductive loads and for high efficiency requirements.

Features & Benefits

  • Double Conversion Online UPS
  • Intelligent Microprocessor Control
  • Wide Input Range
  • True Galvanic Isolation
  • Heavy Duty Charger
  • Cold Start on Battery
  • High Efficiency
  • Compact Size
  • True Sine Wave Output
  • SNMP compactable
  • Suitable for 100% Unbalance Load
  • Suitable for Inductive Load

Capacity
  10 KVA 15 KVA 20 KVA 25 KVA 30 KVA 40 KVA 50 KVA
Input
AC Input 415 V + 15% -20 % Three Phase Input
Frequency 50Hz ± 6%
DC Voltage 360 V DC
Charging Time 8 - 10 Hours for 90% of full Capacity
Charging Type CVCC Internal Controlled Rectifier type
Inverter
Technology IIGBT Double Conversion
Output Voltage 230V AC Single Phase
Frequency 50 Hz ± 0.05 Hz
Voltage Regulation ± 1% for DC Input Variation and Output Load Variation
Wave Form PWM Sine Wave
Harmonic Distortion Less than 3%
Inverter Efficiency > 92 %
Power Factor 0.8
Overload 150 % for 60 Sec
Crest Factor 3:1
Transient Response ± 4% under full load change and corrected within 60 millisec
Audible Noise Less than 45 dB at 1 Meter
Metering  
Microprocessor Based Digital LCD Meter for Output Voltage, Output current & Frequency, DC Voltage & Current, Battery and Load Percentage
Protections  
  Output Overload & Short circuit, Output Under & Overvoltage, DC Under & Overvoltage, Input Under & Overvoltage, Single Phasing & Phase Unbalance
Indications & Alarms  
a) Mains On Indication
b) Inverter On Indication
c) DC Low Indication & Alarm
d) Fault Indication & Alarm
e) Output Overload Indication & Alarm
Bypass Facility  
Manual Bypass Standard Feature
Static Bypass Bi-directional (Optional)
General  
Humidity Max 95%, Non-condensing
Operating Temperature 0°C to 50°C
Dimensions (LxWxH) in mm 710x350x850 1050x350x950 1250x450x1200
Documentation

Download PDF [click here ]