ONLINE UPS FALCON 5000

Falcon 5000 range of IGBT based rectifier Three Phase Online UPS systems are designed, for the data security and business continuity of today’s networked and cloud environment. Its unique modular design and compact footprint comes with variety of special features which are uncommon in this category of UPS Systems.



    • 32 bit DSP controlled UPS
    • IGBT based rectifier
    • Input current THDi < 3%
    • Input PF near unity
    • Inbuilt galvanic isolation
    • Space vector modulation technique
    • 7.2" TFT Graphics Display
    • True RMS reading of more than 25 different parameters of UPS
    • High end interfacing options
    • Superior output quality ; Output voltage distortion < 1%*
    • Unique modular design, offering lowest MTTR
    • Compact system, lowest footprint to kVA ratio in its category
    • Advance thermal design and monitoring
  •  
    Rating in KVA 200 300 400 500 600
    Input
    Nominal Voltage 415 V AC 3 ph+N (± 15%)
    Nominal frequency 50 Hz (46 to 54Hz) (60 Hz Optional)
    Power Factor ≥ 0.99
    THD i < 3%
    Topology 32 bit DSP controlled
    Battery Voltage 600 V DC
    Output
    Power in KW 180 270 360 450 540
    Power Factor 0.6 to Unity within KVA and KW rating
    Voltage 400 V / 415 V AC (± 1%) 3 Ph (380V/ 440 V Optional)
    Frequency 50 Hz (± 0.1 Hz)
    Transient Response ± 5%, recovery within one cycle to 98%
    Waveform Sinusoidal
    Total Harmonic Distortion < 2% max for Linear Load,
    < 3% max for Non-Linear Load (Ref IEEE 62040-3)
    Overload Capacity 110% for 60 min, 125% for 10 min, 150% for 60 sec
    Inverter Efficiency (Ref. IEC 60146-1-1) up to 96%, (ECO mode - up to 98 %)
    Bypass  
    Voltage & Frequency 415 V AC , 15%, 50 Hz (± 2.5%)
    Transfer Time Synchronous mode : No break,
    Asynchronous mode < 10 ms
    Environment  
    Operating Temperature 0 to 40° C
    Storage Temperature 0 to 70° C
    Relative Humidity up to 95% RH (Non-condensing)
    Maximum Operating Altitude 1000 m (without de-rating)
    Acoustic Noise @ 1m (Ref. ISO 3746) < 68 dBA < 70 dBA < 72 dBA < 74 dBA
    Enclosure Protection Grade   IP 20
    Ventilation Forced air cooling
    Cable Entry Bottom
    Dimensions in mm  
    Width 1400 1600 2100 2100
    Depth 900 900 900 1000
    Height 1750 1750 1750 1950
    Cabinet Finish RAL 7016, Texture Finish
    Testing Standards IEC 62040-3
    Communication  
    Interface & Protocol RS 232
    Available Options SNMP, MODBUS, Web based monitoring